Post-Construction HVAC Cleaning: A Turnover Checklist
Drywall dust, sawdust and fireproofing overspray end up in the ductwork. Clean it before turnover, not after the first complaint.
Why new systems fail early
If the HVAC ran during construction — or if ducts sat open on the deck — the system is already loaded with gypsum dust, sawdust and insulation fiber. Gypsum is abrasive and hygroscopic: it scours blower wheels and holds moisture against coils, which is how a brand-new system develops microbial growth in its first cooling season.
The turnover checklist
- Clean all supply and return ductwork by source removal under negative pressure.
- Clean and, where needed, replace flex duct that was left open during framing.
- Wash coils and clean blower wheels and drain pans in every AHU and RTU.
- Replace all construction filters with the specified operating filters.
- Clean grilles, registers and diffusers before ceiling sign-off.
- Verify airflow and balance readings against the design.
- Deliver photo documentation for the closeout binder.
Timing it right
Schedule the clean after final drywall sanding and painting but before ceiling grid close-in wherever possible. Cleaning too early means doing it twice; cleaning after occupancy means doing it around tenants at night rates.
Free Site Assessment
Need a quote for commercial air duct cleaning?
Tell us your facility type, square footage and timing — we'll come out, scope the work and send a written quote with photo documentation.
Keep reading
- Commercial Air Duct Cleaning in Atlanta: A Facility Manager's GuideWhat actually happens during a commercial duct cleaning, how long it takes, and the documentation a facility manager should insist on.
- Commercial Dryer Vent Cleaning: Fire Risk, Insurance and ComplianceWhy lint is a fire-code problem, how often multi-tenant and hospitality dryer vents need service, and what insurers ask for.