Indoor Air Quality
Indoor Air Quality in Office Buildings: What to Measure and Fix
Tenant complaints usually trace back to four measurable things. Here's how to find them and what to do about each.
Four measurements that explain most complaints
- CO2 as a proxy for outside-air delivery — sustained readings above roughly 1,000 ppm point to under-ventilation.
- Relative humidity — Atlanta buildings should hold 40–60%; above that, microbial growth follows.
- Particulate (PM2.5) at the grille versus outdoors, which exposes filtration bypass and dirty ductwork.
- Temperature spread between zones, which usually reveals damper and airflow problems rather than thermostat problems.
Fixes that actually move the numbers
Cleaning coils and restoring airflow usually beats upgrading filters, because a high-MERV filter on a starved system just makes bypass worse. Seal filter racks and access panels, clean the air handler and duct interiors, verify outside-air dampers modulate, and only then raise filtration.
Where microbial growth is confirmed, remediation and UV-C at the coil are appropriate; where it is not, they are an expensive placebo.
Turning it into a program
Baseline the building, fix the mechanical causes, then re-measure and put the readings on a quarterly cadence tied to your filter and PM contract. That record is what defends the building when a tenant escalates.
Free Site Assessment
Need a quote for indoor air quality testing?
Tell us your facility type, square footage and timing — we'll come out, scope the work and send a written quote with photo documentation.
Keep reading
- Commercial Air Duct Cleaning in Atlanta: A Facility Manager's GuideWhat actually happens during a commercial duct cleaning, how long it takes, and the documentation a facility manager should insist on.
- Commercial Dryer Vent Cleaning: Fire Risk, Insurance and ComplianceWhy lint is a fire-code problem, how often multi-tenant and hospitality dryer vents need service, and what insurers ask for.